Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA FINAL/BARRIER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2007 | POOL/SPA FINAL/BARRIER | Approved | IVRS - Inspection :* 1) SVRS #021158 |
|
| 05/23/2007 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) GATES TO BE SELF CLOSING, SELF LATCHING 2) ENTIRE PERIMETER WALL TO BE 5' HIGH MEASURED FROM TOP OF WALL DOOR TO DIRT 3) CANNOT LOCATE #3 & #4 PAPERWORK 4) STOPPED INSPECTION |
|
| 05/08/2007 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) IF NOT USING COMPLETE PERIMETER EXISTING WALL AS PART OF ENCLOSURE, THE FENCE BETWEEN THE HOUSE AND POOL MUST BE 5' HIGH MINIMUM 2) UNABLE TO LOCATE PLANS/PERMIT 3) ALL ITEMS NOT COMPLETE 4) STOPPED INSPECTION |
|
| 04/23/2007 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT HAVE CLIMABLE OBJECTS, FENCES, TREES, ETC.. OUTSIDE OF ENCLOSURE 2) MUST PERMANENTLY CEMENT ROCKS INTO PLACE BELOW METAL FENCING 3) POOL EQUIPMENT LOCATION NOT PER PLAN 4) PANEL NOT LABELED FOR POOL CIRCUIT-NEW SUB PANEL NOT ON PLAN 5) INSTALL ANTI-SIPHON HOSE BIB AT AUTO FILL SOURCE 6) STOPPED INSPECTION-INCOMPLETE |