Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2006 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
| 11/03/2006 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAX SIZE IN 3/4 CONDUIT FOR 4 WIRES IS #8 2) RE-RUN CIRCUIT WITH #8 THHN OR THHW |
|
| 10/18/2006 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* 1) 3/4" CONDUIT 60 AMP #6 = 3 WIRES IN 3/4 OR 50 AMP #8 = 4 WIRES |