Permit: T06BU02333

Parcel: 12510003F


Addresses:

3601 E BROADWAY BL


Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Permit Number - T06BU02333

Inspection Description - REINFORCED MASONRY PRE-GROUT

Inspection Status - Approved

Date Description Inspector Results Comments
11/30/2006 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
12' OK TO GROUT & CAP
11/28/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
WALL @ 8' -- OK TO GROUT*

*GENERAL NOTE: CM-7 STATES THAT REINFORCEMENT TO BE PLACED @ 16" ON CENTER WITH #9 GAUGE SIDE & CROSS RODS AS LISTED IN PLANS.
11/24/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. VERTICALS MUST EXTEND TO TOP OF WALL.
2. PLANS CALL FOR #9 GAUGE LADDER WIRE FOR HORIZONTAL REINFORCEMENT 8" O.C YOU HAVE PLACED IT 18" O.C
REVISE PLAN OR TAKE DOWN BLOCK AND INSTALL PER PLAN.
11/20/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
SCREEN WALL @ 4' -- OK TO GROUT