Inspection History Details
Inspection Status: Approved
Inspection History: REINFORCED MASONRY PRE-GROUT
Permit Number - T06BU02333
Inspection Description - REINFORCED MASONRY PRE-GROUT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/30/2006 | REINFORCED MASONRY PRE-GROUT | Approved | IVRS - Inspection :* 12' OK TO GROUT & CAP |
|
11/28/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* WALL @ 8' -- OK TO GROUT* *GENERAL NOTE: CM-7 STATES THAT REINFORCEMENT TO BE PLACED @ 16" ON CENTER WITH #9 GAUGE SIDE & CROSS RODS AS LISTED IN PLANS. |
|
11/24/2006 | REINFORCED MASONRY PRE-GROUT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. VERTICALS MUST EXTEND TO TOP OF WALL. 2. PLANS CALL FOR #9 GAUGE LADDER WIRE FOR HORIZONTAL REINFORCEMENT 8" O.C YOU HAVE PLACED IT 18" O.C REVISE PLAN OR TAKE DOWN BLOCK AND INSTALL PER PLAN. |
|
11/20/2006 | REINFORCED MASONRY PRE-GROUT | Partial Approval | IVRS - Inspection :* SCREEN WALL @ 4' -- OK TO GROUT |