Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - ALARM FINAL
Permit Number - T06BU02104
Inspection Description - FIRE - ALARM FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/17/2007 | FIRE - ALARM FINAL | Approved | ||
| 04/11/2007 | FIRE - ALARM FINAL | Cancelled | IVRS - RI canceled | |
| 04/09/2007 | FIRE - ALARM FINAL | Denied | 1. ON FIRST FL STOBES FAILED TO WORK ON BATTERY POWER NEED TO REPAIR POWER BOOSTER #3 2. NO LOCK OUT ON BREAKERS FOR ALARM SYSTEM 3. SYSTEM FAILED TO SHOW TROUBLE FOR LOW BATTERY OR NO BATTERY. NO NOTICE WAS GIVEN WHEN WE FOUND BATTIES MISSING IN POWER BOOSTER #3. 4. STILL NEED TO TEST TAMPER SWITCHES 5. REPLACE BROKEN HORN/STOBE IN SHIPPING AREA BY EXIT DOOR |