Inspection Status: Approved
Inspection History: FIRE SPKLR - OH PIPING & HYDRO
| Date |
Description |
Inspector |
Results |
Comments |
| 04/26/2010 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Approved |
MC Fire given new Cals showing head can work to 8 foot off wall. |
| 04/21/2010 |
FIRE SPKLR - OH PIPING & HYDRO |
|
Denied |
1st floor bedroom by front entrance door head to far off wall 8' needs to be 7' off wall. Add head, move head or find new heads that can give proper coverage. Will need cut sheet for new heads. |