Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T06BU02019
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/26/2010 | FIRE SPKLR - FINAL | Approved | MC Fire given new Cals showing head can work to 8 foot off wall. | |
04/21/2010 | FIRE SPKLR - FINAL | Denied | 1. Kitchen heads south wall to far off wall 7' 9" need to be 7' move heads. Add heads or find new head to meet coverage, will need cut sheet for new heads. 2. 1st floor bedroom head to far 7' 6" needs to be 7'. Add heads or new head with cut sheet showing 8' off wall. |