Permit: T06BU02019

Parcel: 108252390

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T06BU02019

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/26/2010 FIRE SPKLR - FINAL Approved MC Fire given new Cals showing head can work to 8 foot off wall.
04/21/2010 FIRE SPKLR - FINAL Denied 1. Kitchen heads south wall to far off wall 7' 9" need to be 7' move heads. Add heads or find new head to meet coverage, will need cut sheet for new heads.
2. 1st floor bedroom head to far 7' 6" needs to be 7'. Add heads or new head with cut sheet showing 8' off wall.