Permit: T06BU01854

Parcel: 136404880

Inspection Status: Approved

Inspection History: POOL/SPA FINAL/BARRIER

Permit Number - T06BU01854

Inspection Description - POOL/SPA FINAL/BARRIER

Inspection Status - Approved

Date Description Inspector Results Comments
11/08/2006 POOL/SPA FINAL/BARRIER Approved IVRS - Inspection :*
11/07/2006 POOL/SPA FINAL/BARRIER Partial Approval IVRS - Inspection :*
1) BOND FENCE ON SOUTH SIDE
2) SVRS S/N #019405
3) OK TO PLASTER
10/20/2006 POOL/SPA FINAL/BARRIER Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NEED MINIMUM 5' BARRIER MEASURED FROM OUTSIDE
2) GATES MUST OPEN OUT AND BE SELF CLOSING
3) ELECTRIC NOT COMPLETE
4) NEED T/P VALVE ON HEATER
5) NEED MINIMUM 20 POUND TEST ON PLUMBING
6) COULD ADD 3 1/2" WROUGHT IRON TO TOP OF WALL OR INSTALL 6' WROUGHT IRON FENCE 20" FROM NORTH EDGE OF POOL