Permit: T06BU01549


Addresses:

2008 E RIVER RD


Inspection Status: Approved

Inspection History: MODULAR - ELECTRIC INSPECTION

Permit Number - T06BU01549

Inspection Description - MODULAR - ELECTRIC INSPECTION

Inspection Status - Approved

Date Description Inspector Results Comments
10/20/2006 MODULAR - ELECTRIC INSPECTION Approved IVRS - Inspection :*
10/19/2006 MODULAR - ELECTRIC INSPECTION Not ready for Inspection IVRS - Inspection :*
NO ACCESS
10/18/2006 MODULAR - ELECTRIC INSPECTION Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
THIS TYPE OF WIRE/CABLE IS NOT LISTED TO BE BURIED IN EARTH -- TEMPORARY OR NOT ALL WIRING TO TRAILER AND SCATTER BOX TO BE BE RAN IN AN APPROVED WIRING METHOD. IT ALSO APPEARS TO HAVE SEVERAL OTHER CODE VIOLATIONS - I.E BREAKER NOT MARKED, PROPER CONNECTOR/FITTING NOT USED, IMPROPER OVERCURRENT PROTECTION ETC, ETC,

NOTE: DO NOT ENERGIZE ANY FEEDERS THAT HAVE NOT BEEN INSPECTED AND APPROVED. MAKE CORRECTIONS AND CALL FOR REINSPECTION BY 10/20/06 OR POWER WILL BE DISCONNECTED.