Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - KITCHEN EXH HOOD FINAL
Permit Number - T06BU01497
Inspection Description - FIRE - KITCHEN EXH HOOD FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/26/2010 | FIRE - KITCHEN EXH HOOD FINAL | Approved | 8" plate added and holes patched | |
| 05/11/2010 | FIRE - KITCHEN EXH HOOD FINAL | Denied | 1. Spacing between open flame 7 deep fryer 16" or more or install 8" plate. 2. Opening above filters shall be grease tight seal holes where piping is located northeast end & 1/2" pipe all the way across. |