Permit: T06BU00992

Parcel: 130055810


Addresses:

2333 E 36TH ST

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
05/05/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
05/02/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SITE PLAN SHOWS 6'-8" TO EDGE OF ROOF FROM PROPERTY LINE. YOU HAVE APPROXIMATELY 4'8" REVISE PLAN OR RELOCATE COLUMNS.
2. FOOTING PLANS CALL FOR 36"X36" FOOTINGS WITH 4 #4 REBAR EACH WAY. YOU HAVE ONLY INSTALLED 2 #4 EACH WAY