Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T06BU00987
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
05/16/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. EQUIPMENT GROUND FOR POOL SUB-PANEL TO BE GREEN OR BARE ENTIRE LENGTH -- NEC 250.119 2. PROVIDE HOLD DOWN DEVICE FOR BACK FED MAIN BREAKER NEC 408.16F 3. PROVIDE GROUNDING ELECTRODE SYSTEM FOR SUB-PANEL NEC 250.50, 250.32 4. CORRECTLY IDENTIFY CIRCUIT DIRECTORY -- NEC 408.4 5. TIGHTEN ALL BONDING CONNECTIONS - NEC 110 6. TIGHTEN ALL FITTINGS - NEC 110 7. WEATHERPROOF BOX IS OVERFILLED AND UNGROUNDED NEC 314.16, 250 8. INSTALL SPA E-STOP ADJACENT TO AND WITHIN SIGHT OF SPA - SHOULD SAY "SPA EMERGENCY SHUT OFF - SEE NEC 680.41 9. TIMER TOO CLOSE TO SPA - NEC 680.22C |
|
04/30/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK GROUND & COMPOUND FOR POOL & SPA LIGHTS OK TO FILL WITH WATER: CALL FOR FINAL WHEN WATER IS IN AND POOL AND SPA ARE FULLY OPERATIONAL |
|
04/03/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* OK TO POUR DECK |