Permit: T06BU00987

Parcel: 105123390


Addresses:

4133 N STONE AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/21/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/16/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. EQUIPMENT GROUND FOR POOL SUB-PANEL TO BE GREEN OR BARE ENTIRE LENGTH -- NEC 250.119
2. PROVIDE HOLD DOWN DEVICE FOR BACK FED MAIN BREAKER
NEC 408.16F
3. PROVIDE GROUNDING ELECTRODE SYSTEM FOR SUB-PANEL
NEC 250.50, 250.32
4. CORRECTLY IDENTIFY CIRCUIT DIRECTORY -- NEC 408.4
5. TIGHTEN ALL BONDING CONNECTIONS - NEC 110
6. TIGHTEN ALL FITTINGS - NEC 110
7. WEATHERPROOF BOX IS OVERFILLED AND UNGROUNDED
NEC 314.16, 250
8. INSTALL SPA E-STOP ADJACENT TO AND WITHIN SIGHT
OF SPA - SHOULD SAY "SPA EMERGENCY SHUT OFF -
SEE NEC 680.41
9. TIMER TOO CLOSE TO SPA - NEC 680.22C
04/30/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK GROUND & COMPOUND FOR POOL & SPA LIGHTS
OK TO FILL WITH WATER: CALL FOR FINAL WHEN WATER IS IN AND POOL AND SPA ARE FULLY OPERATIONAL
04/03/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
OK TO POUR DECK