Permit: T06BU00987

Parcel: 105123390


Addresses:

4133 N STONE AV


Inspection Status: Approved

Inspection History: ELECTRIC - UNDERGROUND

Permit Number - T06BU00987

Inspection Description - ELECTRIC - UNDERGROUND

Inspection Status - Approved

Date Description Inspector Results Comments
05/21/2007 ELECTRIC - UNDERGROUND Approved IVRS - Inspection :*
05/16/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
04/30/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
04/03/2007 ELECTRIC - UNDERGROUND Not ready for Inspection IVRS - Inspection :*
03/30/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. USE LUG LISTED FOR DIRECT BURIAL FOR HANICAP JIG
2. TIGHTEN ALL BONDING CONNECTIONS.
03/19/2007 ELECTRIC - UNDERGROUND Partial Approval IVRS - Inspection :*
OK RACEWAYS AND BONDING -- NEED BONDING INSPECTION BEFORE DECK POUR.
02/21/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/16/2007 ELECTRIC - UNDERGROUND Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. COMPLETELY EXPOSE ALL UNDERGROUND RACEWAYS
INCLUDING TO LIGHT FIXTURES TO POOL & SPA.
2. BOND CLAMP TO CONNECT TO SINGLE PIECE OF REBAR AND ALL SCREWS TIGHTENED.

NEED 18" DEPTH FOR ALL RACEWAY UNDERGROUND.