Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
Permit Number - T06BU00987
Inspection Description - ELECTRIC - UNDERGROUND
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/21/2007 | ELECTRIC - UNDERGROUND | Approved | IVRS - Inspection :* | |
05/16/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
04/30/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
04/03/2007 | ELECTRIC - UNDERGROUND | Not ready for Inspection | IVRS - Inspection :* | |
03/30/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. USE LUG LISTED FOR DIRECT BURIAL FOR HANICAP JIG 2. TIGHTEN ALL BONDING CONNECTIONS. |
|
03/19/2007 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* OK RACEWAYS AND BONDING -- NEED BONDING INSPECTION BEFORE DECK POUR. |
|
02/21/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
02/16/2007 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. COMPLETELY EXPOSE ALL UNDERGROUND RACEWAYS INCLUDING TO LIGHT FIXTURES TO POOL & SPA. 2. BOND CLAMP TO CONNECT TO SINGLE PIECE OF REBAR AND ALL SCREWS TIGHTENED. NEED 18" DEPTH FOR ALL RACEWAY UNDERGROUND. |