Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T06BU00814
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/22/2007 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* | |
05/18/2007 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : There is no access to the site.| 920* NO ACCESS TO POOL AREA ALL GATES LOCKED PLEASE MEET WITH INSPECTOR ON SITE |
|
04/20/2007 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. EMT & FITTINGS IN CONTACT WITH EARTH. NEED CORROSION PROTECTION NEC 358.10 2. CONNECT GROUND WIRE TO METAL JUNCTION BOX AT PUMP DISCONNECTS 3. INSTALL GROUND LUG KIT AT PUMP DISCONNECTS 4. INSTALL FLASH WARNING AT POOL PANEL NEC 110.16 5. CANNOT SEE GROUND CONNECTION AT LIGHT NICHES. POOL FILLED. 6. CANNOT CHECK CORD LENGTH AT POOL LIGHT. POOL FILLED 7. HOW MANY LIGHT CIRCUITS TO POOL? HOW MANY LIGHTS AND WATTAGE ON CIRCUITS? |
|
02/02/2007 | POOL/SPA ELECTRIC | Partial Approval | 1) ALL ITEMS IN COOL DECKING OK | |
01/29/2007 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* OK UNDERGROUND CONDUITS PLEASE CALL FOR COOL DECK INSPECTION |
|
01/12/2007 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* ADDRESS TO BE CHANGED BY NEXT INSPECTION OK TO GUNITE 1. PVC GLUE TO HAVE ELECTRICAL LISTING |
|
01/10/2007 | POOL/SPA ELECTRIC | Not ready for Inspection | IVRS - Inspection :* 1. HAVE ADDRESS CHANGED TO CORRECT LOCATION 2. NO MORE THAN 360' IN A CONDUIT RUN 3. TIGHTEN ALL BOND CONNECTIONS 4. WHERE ARE ECTUCTIONS FOR HANDRAILS IN POOL 5. PLEASE USE GLUE THAT IS LISTED FOR USE WITH ELECTRICAL. 6. ABOVE GRADE PVC TO BE SCHEDULE 80 *NOTE: WILL NEED TO DO COOL DECK INSPECTION TO CHECK ECTUCTIONS. |