Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA ELECTRIC
Permit Number - T06BU00813
Inspection Description - POOL/SPA ELECTRIC
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/29/2006 | POOL/SPA ELECTRIC | Approved | IVRS - Inspection :* 1) SVRS S/N #014413 |
|
10/25/2006 | POOL/SPA ELECTRIC | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. BONDING CONNECTIONS TO GRAB RAIL CMPS AND POOL LIGHT WERE NEVER INSPECTED -- ONLY WHIPS AT PRE-GUNITE INSPECTION. 2. UNDERGROUND FOR POOL - PANEL NOT INSPECTED BEFORE COVER. 3. NEED GFI PROTECTED 120V RECEPTACLE BETWEEN 10 & 20' OF POOL -- NEC 680.22 4. PROVIDE GFI PROTECTION FOR AREA LIGHTING AS REQUIRED -- NEC 680.22 B4 A-3 5. IDENTIFY PANEL DIRECTORY -- NEC 408.4 6. TIGHTEN CONNECTIONS IN PANEL -- NEC 110 7. IDENTIFY POOL SUB PANEL @ SERVICE -- NEC 408.4 & STRAP PIPE 8. RAMADA; POOL PANEL WIRING INCOMPLETE CAN'T WALK IN POOL FOR LIGHT FIXTURE INSPECTION AT THIS TIME. DO NOT FILL OR USE POOL. 9. POOL LIGHT NEEDS GFI PROTECTION |
|
10/24/2006 | POOL/SPA ELECTRIC | Cancelled | IVRS - RI canceled | |
09/07/2006 | POOL/SPA ELECTRIC | Partial Approval | IVRS - Inspection :* POOL BOND CONNECTIONS TO REBAR BEFORE GUNITE OK TO GUNITE 7-SIDE WHIPS (NO JIGS) POOL LIGHT BONDING EQUIPMENT BOND RUN ALSO, OK POOL LIGHT RACEWAY (BRASS) COVER BOND @ BOTTOM FOR HANDRAIL @ STEPS |