Permit: T06BU00813


Addresses:

2981 E ALLEN RD


Inspection Status: Approved

Inspection History: POOL/SPA ELECTRIC

Permit Number - T06BU00813

Inspection Description - POOL/SPA ELECTRIC

Inspection Status - Approved

Date Description Inspector Results Comments
10/29/2006 POOL/SPA ELECTRIC Approved IVRS - Inspection :*
1) SVRS S/N #014413
10/25/2006 POOL/SPA ELECTRIC Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. BONDING CONNECTIONS TO GRAB RAIL CMPS AND POOL LIGHT WERE NEVER INSPECTED -- ONLY WHIPS AT PRE-GUNITE INSPECTION.
2. UNDERGROUND FOR POOL - PANEL NOT INSPECTED BEFORE COVER.
3. NEED GFI PROTECTED 120V RECEPTACLE BETWEEN 10 & 20' OF POOL -- NEC 680.22
4. PROVIDE GFI PROTECTION FOR AREA LIGHTING AS REQUIRED -- NEC 680.22 B4 A-3
5. IDENTIFY PANEL DIRECTORY -- NEC 408.4
6. TIGHTEN CONNECTIONS IN PANEL -- NEC 110
7. IDENTIFY POOL SUB PANEL @ SERVICE -- NEC 408.4 & STRAP PIPE
8. RAMADA; POOL PANEL WIRING INCOMPLETE
CAN'T WALK IN POOL FOR LIGHT FIXTURE INSPECTION AT THIS TIME. DO NOT FILL OR USE POOL.
9. POOL LIGHT NEEDS GFI PROTECTION
10/24/2006 POOL/SPA ELECTRIC Cancelled IVRS - RI canceled
09/07/2006 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
POOL BOND CONNECTIONS TO REBAR BEFORE GUNITE
OK TO GUNITE
7-SIDE WHIPS (NO JIGS)
POOL LIGHT BONDING
EQUIPMENT BOND RUN
ALSO, OK POOL LIGHT RACEWAY (BRASS) COVER
BOND @ BOTTOM FOR HANDRAIL @ STEPS