Permit: T06BU00710

Parcel: 140324850

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Permit Number - T06BU00710

Inspection Description - EXCAVATION/LAYOUT REBAR & ZON

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2006 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
05/09/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
TAKE THIS SKETCH TO PLAN REVIEW.
1. YOUR PLANS DO NOT APPEAR TO ACCOUNT FOR UPPER SCREEN WALL SURCHARGE FOR P.L WALL NOR DOES POOL DESIGN APPEAR TO ACCOUNT FOR SURCHARGE OR NEW RETAINING WALL.
5'3" FROM UPPER GRADE TO BOTTOM OF NEW RETAINING FOOTING.
EDGE OF RETAIN FOOTING BUTTS POOL WALL.
05/04/2006 EXCAVATION/LAYOUT REBAR & ZON Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. INSTALL DOBIES PROPERLY YOU NEED 3" CLEAR FROM STEEL TO EARTH.
2. PROVIDE A POOL REINFORCEMENT PLAN THAT CALCULATES SURCHARGES IMPOSED BY RETAINING WALL.