Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
07/20/2006 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
07/19/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. REBAR IN VERTICAL CELLS MUST GO TO TOP OF MASONRY COLUMN.
2. YOUR ANCHOR BOLTS OR STRAPS FOR BEAM MUST BE INSTALLED BEFORE GROUTING.
3. LAP SPLICE FOR #4 REBAR IN MASONRY IS 24"