Permit: T06BU00396

Parcel: 133482840

Inspection Status: Denied

Inspection History: POOL/SPA ELECTRIC

Date Description Inspector Results Comments
04/19/2006 POOL/SPA ELECTRIC Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SUBPANEL REQUIRES ISOLATED BONDING BAR AND NEUTRAL.
2. IDENTIFY BOTH ENDS OF NEUTRAL WIRE WITH WHITE TAPE.
3. CONDUIT FITTING INTO SIDE OF SUBPANEL MUST BE WEATHERPROOF TYPE.
4. SECURE EMT WITHIN 18" OF SUBPANEL.
04/05/2006 POOL/SPA ELECTRIC Partial Approval IVRS - Inspection :*
1) GROUND WIRES OK
2) PVC CONDUIT MUST BE AT LEAST 18" DEEP OR COVERED WITH CONCRETE (AREA NEAR FILTER)
3) EQUIPMENT NOT BONDED
4) INSTALL BLUE TRACER WIRE ON SUPPLY LINE WHEN RUN TO SUPPLY SOURCE