Inspection History Details
Inspection Status: Approved
Inspection History: POOL/SPA PRE-GUNITE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/03/2006 | POOL/SPA PRE-GUNITE | Approved | IVRS - Inspection :* | |
| 08/02/2006 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection : See detailed listing on site.| 999* O TEST H20 PIPING FLOOR DRAINS TO BE MIN. 36" BETWEEN FINISHED COVERS APPROX 48" BETWEEN PIPING. |
|
| 07/31/2006 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection : See detailed listing on site.| 999* TOO WET DRY OUT - RECALL INCOMPLETE (SEE PREVIOUS PAPER WORK) |
|
| 07/24/2006 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) ELECTRIC NOT RUN FROM SOURCE TO EQUIPMENT 2) LOW PRESSURE TEST ON H20 SYSTEM 3) ELECTRIC TO POOL COVER NOT INSTALLED 4) PLAN CALLS FOR GAS STUB TO BBQ 5) 1" CONDUIT TO FUTURE SPA OK 6) BOTTOM FLOOR DRAINS TO BE MINIMUM 36" BETWEEN COVERS 7) STOPPED INSPECTION |
|
| 04/26/2006 | POOL/SPA PRE-GUNITE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) POOL DEPTH 4' TO HAVE VERTICAL #3 REBAR AT 6" ON CENTER SPACING 2) GAS PIPING TO HAVE MINIMUM 24" OF COVER-INSTALLED GAS PIPING IN TRENCH 3) NEED TO KNOW DEMAND FOR GAS APPLIANCE TO DETERMINE SIZE OF PIPING 4) ELECTRIC NOT RUN TO EQUIPMENT 5) PLASTIC CONDUIT TO HAVE 12" COVER 6) STOPPED INSPECTION |