Inspection History Details
Inspection Status: Partial Approval
Inspection History: POOL/SPA FINAL/BARRIER
Permit Number - T06BU00069
Inspection Description - POOL/SPA FINAL/BARRIER
Inspection Status - Partial Approval
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/19/2006 | POOL/SPA FINAL/BARRIER | Partial Approval | IVRS - Inspection :* 1) CHANGE GATE ON WEST SIDE TO OPEN OUT AND BE SELF CLOSING 2) SVRS NOT REQUIRED-ALTERNATE ENGINEERED SYSTEM 3) OK TO PLASTER |
|
06/15/2006 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
06/14/2006 | POOL/SPA FINAL/BARRIER | Denied | IVRS - Inspection : See detailed listing on site.| 999* |