Inspection History Details
Inspection Status: Approved
Inspection History: EXCAVATION/LAYOUT REBAR & ZON
Permit Number - T06BU00018
Inspection Description - EXCAVATION/LAYOUT REBAR & ZON
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/01/2006 | EXCAVATION/LAYOUT REBAR & ZON | Approved | IVRS - Inspection :* | |
01/30/2006 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. NEED TO HAVE (2) 3/8" X 9" STEEL RODS (REBAR) OR BOLTS NEAR BOTTOM OF POST PER DETAIL AG ON PAGE 6 OF APPROVED BUILDING DOCUMENTS. EACH POST CURRENTLY HAS ONE THEY NEED TO BE PERPENDICULAR TO EACH OTHER. |
|
01/25/2006 | EXCAVATION/LAYOUT REBAR & ZON | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. SHADE CANOPY CONSTRUCTION DOCUMENTS NEED TO BE APPROVED & STAMPED BY THE CITY OF TUCSON. IT APPEARS THAT ONLY THE GRADING/ZONING (8 1/2" X 11") PAPER IS APPROVED. 2. POSTS MUST HAVE 3" OF CLEARANCE FROM EARTH (IN ALL DIRECTIONS) PRIOR TO PLACEMENT OF CONCRETE |