Case: T05VL01283

Parcel: 127035560


Addresses:

5555 E 5TH ST


Inspection Status: Compliance

Inspection History: FOLLOW UP CODE VIOLATION

Case Number - T05VL01283

Inspection Description - FOLLOW UP CODE VIOLATION

Inspection Status - Compliance

Date Description Inspector Results Comments
02/28/2006 FOLLOW UP CODE VIOLATION Compliance MAY CLOSE CASE WHEN TEMPORARY FENCE PANELS ARE PAID FOR
01/30/2006 FOLLOW UP CODE VIOLATION Approved F.U. 30 DAYS -- 1. OWNER HAS COVERED DAMAGED AREA AND REMOVED ROOF JACKS SUPPORTING STRUCTURE. UNFORTUNATELY NO REPAIR PERMITS WERE OBTAINED AND NO INSPECTIONS WERE PERFORMED TO VERIFY THE SAFETY OF THE STRUCTURE.
2. LARSEN BAKER MANAGEMENT WAS CONTACTED BUT NO ONE WAS IN OFFICE WHO COULD PROVIDE ANY INFORMATION ABOUT NON-PERMITTED WORK.
3. CANYON FENCE CALLED TO FENCE OFF AREA AROUND DAMAGED COLUMN THAT COULD BE AFFECTED IN A COLLAPSE. I BELIEVE THIS TO BE NECESSARY AS A MAIN STRUCTURAL SUPPORT IS NOW HIDDEN AND THERE IS NO WAY TO VERIFY PROPER REPAIR.
4. OWNER OF PROPERTY TO BE CITED FOR WORK WITHOUT PERMITS AND FENCING NOT TO BE REMOVED UNTIL PROPER PERMITS AND INSPECTIONS ARE OBTAINED.
12/28/2005 FOLLOW UP CODE VIOLATION Violation 12/27/05 -- 1. SUPPORT JACKS HAVE NOT BEEN PLACED TO SUPPORT BEAM AS REQUESTED BY THIS INSPECTOR, AND THEY DO NOT APPEAR TO BE HOLDING ANYTHING STRUCTURAL.
2. YOU MUST NOW HAVE A REGISTERED ENGINEER DESIGN TEMPORARY SUPPORTS AND INSTALL THEM TODAY! FAILURE TO PROPERLY SUPPORT BEARING BEAM WILL RESULT IN CLOSURE OF STORE DUE TO POSSIBILITY OF FURTHER COLLAPSE AND DAMAGE TO ELECTRICAL SYSTEM. THIS IS A FIRE HAZARD AS WELL AS A STRUCTURAL HAZARD.
3. CONTACTED LARSEN BAKER @ 296-0200 10:15 AM MAINT. PERSON "GEORGE" IS TO CONTACT ME TODAY.