Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T05VL00609

Parcel: 128150520


Addresses:

5337 E DOUGLAS ST

Inspection Status: Closed

Inspection History: INITIAL CODE VIOLATION

Date Description Inspector Results Comments
07/20/2005 INITIAL CODE VIOLATION Closed 7/19/05 -- ARRIVED AT SITE TO FIND THAT FIRE WAS CONTAINED IN OLD BREAKER PANEL CONVERTED TO J-BOX
AN AL/CU SPLICE WAS MADE WITH IMPROPER CONNECTOR AND WITHOUT REQUIRED ELECTROLUX COATING ON AL WIRE
HIGH HAZARD ABATED BY CUTTING POWER AT METER AND OWNER TOLD TO HAVE LICENSED ELECTRICIAN MAKE PROPER SPLICE BEFORE RE-ENERGIZING - OWNER CALLED ELECTRICIAN - NO F.U. REQUIRED -- CLOSE CASE