Inspection Status: Violation
Inspection History: FOLLOW UP CODE VIOLATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2006 | FOLLOW UP CODE VIOLATION | Violation | SITE VISIT TO THIS ILLEGALLY CONSTRUCTED WAREHOUSE FOUND A GENERATOR CONNECTED BY EXTENSION CORD TO ELECTRIC SUB-PANEL. THIS STEEL BUILDING IS NOT PROPERLY GROUNDED NOR BONDED FOR ELECTRIC SERVICE AT ANY KIND. TELEPHONE CONVERSATION WITH D. SANTA CRUZ, ELECTRICAL INSPECTOR CONFIRMED HAZARDOUS WIRING TO GENERATOR AND UNSAFE CONDITION OF BUILDING. FOUR EACH DOORS 2 ROLL-UP AND 2 SIDE HUNG WERE POSTED "DO NOT ENTER UNSAFE TO OCCUPY" ALSO, EXTENSION CORD WAS REMOVED FROM GENERATOR A MR. TIM BENEDICT WAS AT SITE AND CLAIMED TO BE PROPERTY MANAGER. HE HAS BEEN GIVEN COPY OF THIS REPORT. POSTING OF PROPERTY WITNESSED BY BOB RICH |
|
| 04/19/2006 | FOLLOW UP CODE VIOLATION | Violation | 10:30 AM MEETING HELD AT SITE WITH BRENT (REPRESENTING OWNER) STEVE LONG, ROBERT RICH, RAY MAJUTA, ANDY CONNOR, MYSELF AND ELIZABETH EBERBACH. A MORE THOROUGH INSPECTION WAS DONE AND SOME ADDITIONAL VIOLATIONS NOTED. STEVE LONG WILL BE RECOMPILING VIOLATION LIST AND THEN WE WILL SUBMIT FOR CITATION WITH CITY PROSECTOR LIN SCHARBACH. BUILDING & POWER IS STILL UNDER STOP WORK ORDER. |