Inspection History Details
Inspection Status: Closed
Inspection History: FOLLOW UP CODE VIOLATION
Case Number - T05VL00339
Inspection Description - FOLLOW UP CODE VIOLATION
Inspection Status - Closed
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/30/2005 | FOLLOW UP CODE VIOLATION | Closed | CLOSE CASE | |
| 08/01/2005 | FOLLOW UP CODE VIOLATION | Violation | WORK IN PROGRESS KEEP OPEN, F.U. 30 DAYS | |
| 06/28/2005 | FOLLOW UP CODE VIOLATION | Violation | NO ACTIVITY ON SITE F/U 30 DAYS | |
| 05/18/2005 | FOLLOW UP CODE VIOLATION | Violation | 5/12/05-PERMITS REQUIRED FOR ELECTRIC, MECHANICAL, PLUMBING AND STRUCTURE SEE HECTOR LEYVA FOR GROUND INSPECTION REPORTS-ATTACHED ------------------------------------------------------------------------------------------------- 5/12/05-REPORT FROM INSPECTOR M. CAPISTRAN: ELECTRICAL MUST BE UPGRADED. THE NUMBER OF DISCONNECTS EXCEEDS THE MAXIMUM OF 6 EXTERIOR LIGHT IS IN DIS-REPAIR AND DOES NOT MEET LIGHTING CODE STANDARDS EXTERIOR WALL LIGHT FIXTURES ARE NOT CONSTRUCTED TO RESIST THE WEATHER EXIT LIGHTING IS MISSING MANY LIGHTING FIXTURES ARE ZIP CORD AND CAP CONNECTED ZIP CORD USED FOR PERMANENT WIRING M/C CABLE RUN ACROSS FLOOR CIRCUITRY FOR A/C, REFRIGERATION, AND KITCHEN APPLIANCES IS NEEDED ------------------------------------------------------------------------------------------------- 5/12/05-REPORT FROM INSPECTOR C. WILLIAMS: NEW A/C EQUIP (3) ON ROOF TOP NEW TYPE I HOOD, 16 GA. EXHAUST DUCT VTR INTO NEW CURB. ?? NO VERIFICATION OF RATED CHASE NEW WALK-IN CONDENSOR ON ROOF |