Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/29/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 12/27/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ROOF FLUSHING REQUIRED AT ROOF PENETRATIONS WEATHER PROOF PIPE SUPPORTS REQUIRED AGA VALUES REQUIRED SECURE VENT AT WATER HEATER PROVIDE BONDING OF GAS LINE RAISE VENT PIPING FOR FURNACE & WATER HEATER TO 3' ABOVE COOLER. DOUBLE WALL B VENT W/LISTED CAP REQUIRED RETEST AND RECALL FOR INSPECTION |