Permit: T05PL02081

Parcel: 136310260

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Permit Number - T05PL02081

Inspection Description - PLUMBING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
12/30/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
12/29/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PIPING UNDER TRAILER REQUIRES SUPPORT AT 32"
COMPLETE INSTALLATION OF VACUUM BREAKERS
DRIP AT KIT. SINK FAUCET
12/28/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PEX SHOULD NOT BE UNDER STRAIN
2) T 3-2 REQUIRES PEX TO BE SUPPORTED AT 32". THE STANDARDS ARE NOT LESS FOR MOBILE HOME INSTALLATIONS
3) PIPE INSULATION IS FALLING OFF IN PLACES AND THERE ARE MANY GAPS IN THE INSULATION
4) ENERGY CONSERVATION REQUIREMENTS INCLUDE INSULATING BOTH HOT AND COLD PIPING WITHIN 8' OF WATER HEATER