Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/26/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 12/22/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 10 PSI AT 9:03 AM 9-5 PSI AT 9:15 - LEAK IS APPARENT REMOVE OLD PLUG VALVES, PROVIDE AGA GAS SHUT OFF VALVES. REPLACE PIPING & FLEX BURIED IN CONCRETE PATCH ON WALL PROVIDE ACCESSIBLE AGA SHUT OFF VALVE BEHIND STOVE PROTECTION OF OUTDOOR EQUIPMENT IS PROVIDED BY OVERHEAD ROOF, 5108 WALL EXTEND VENT TERMINATION ABOVE PARAPET WALL REMOVE TAPE FROM TRANSITION OF SINGLE WALL TO DOUBLE WALL VENT AT WATER HEATER. SUPPORT GAS PIPING AT METER TO KEEP IT OFF THE GROUND RETEST FOR LEAKS, PROVIDE PRESSURE TEST RECALL FOR INSPECTION WHEN READY |