Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/26/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
12/22/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
10 PSI AT 9:03 AM
9-5 PSI AT 9:15 - LEAK IS APPARENT
REMOVE OLD PLUG VALVES, PROVIDE AGA GAS SHUT OFF VALVES.
REPLACE PIPING & FLEX BURIED IN CONCRETE PATCH ON WALL
PROVIDE ACCESSIBLE AGA SHUT OFF VALVE BEHIND STOVE
PROTECTION OF OUTDOOR EQUIPMENT IS PROVIDED BY OVERHEAD ROOF, 5108 WALL
EXTEND VENT TERMINATION ABOVE PARAPET WALL
REMOVE TAPE FROM TRANSITION OF SINGLE WALL TO DOUBLE WALL VENT AT WATER HEATER.
SUPPORT GAS PIPING AT METER TO KEEP IT OFF THE GROUND
RETEST FOR LEAKS, PROVIDE PRESSURE TEST
RECALL FOR INSPECTION WHEN READY