Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/21/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* PETITION OF APPEAL #2005.290 ON SITE 18 PSI TEST UNDERGROUND UP AT BUILDING TO FIREPLACE LOG LIGHTING, WATER HEATER & FURNACE ONLY - OK S.W. GAS 889-1888 - GAS CARD @ METER |
|
| 12/20/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :*PIPING IN GROUND OK TO COVER, PRESSURE TEST HOLDING 20 PSI BONDING REQUIRED ON GAS LINE T & P RELIEF VALVE MUST GRAVITY DRAIN TO EXTERIOR XL T & P REQUIRE IF PIPED W/TEE ABOVE HEATER. PIPE ON ROOF REQUIRED WEATHER PROOF SUPPORTS @ 8' ?? FURNACE FLUE SHALL TERMINATE 1' ABOVE GRAVITY AIR INLET. REMOVE OLD PLUG COCK TO FIRE PLACE LOG LIGHTER REQUIRES VALVE TO REACH AB/? FROM LIGHTING AREA RETEST SYSTEM AFTER MAKING CORRECTIONS RE CALL FOR INSPECTIONS. |
|
| 12/19/2005 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* |