Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/14/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* CALL SW GAS 889-1888 |
|
| 04/04/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* GAUGE PRESSURE DROPPING USE TAPE & DOPE ON JOINTS |
|
| 03/31/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* HAVE PRESSURE ON SYSTEM BEFORE INSPECTION. |
|
| 03/31/2006 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* GAGE DROPPED TO 3.5 CHECK FOR LEAKS WITH SOAPY WATER |
|
| 03/08/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* SECURE VENT CONNECTOR TO VENT W/SCREWS. NO TAPE AT TRANSITION PRESSURE TEST DROPPING |
|
| 02/16/2006 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) VENT FROM FURNACE TO BE DBL WALL TO POINT OF TERMINATION 2) PROVIDE ROOF FLASHINGS ON PENETRATIONS THRU ROOF AT GAS PIPE 3) PROVIDE 3 GALVANIZED SCREWS AT EACH JOINT OF FURNACE VENT PIPING |
|
| 12/20/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE PRESSURE TEST ON GAS SYSTEM PROVIDE APPROVED LISTED METAL VENT CONNECTOR AT FURNACE, PROVIDE PROPER SLOPE ON VENT CONNECTOR - NO DIPS OR SAGS. PROVIDE BONDING OF GAS PIPE PROVIDE AN AGA RATED VALVE AT STOVE |