Permit: T05PL02041

Parcel: 106040560

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/19/2005 PLUMBING - FINAL Approved IVRS - Inspection :*GAS CARD LEFT ON 12/16/05 BY MYERS
12/16/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1) TEN POUND PRESSURE TEST ON THE SYSTEM REQUIRED
2) A THREAD PROTECTOR IS NOT A COUPLING. USE A STD TAPER THREADED FITTING
3) USE A ROOF JACK AT ROOF. USE A STD TAPER THREADED FITTING
4) NEED A SHUT OFF VALVE AT THE COLD INLET
5) REQUIRE A BOND BETWEEN GAS AND WATER PIPING
6) SUPPORT ROOF TOP GAS
7) APPROVED VALVE REQUIRED/AGA CSA