Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/27/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :*WATER HTR. VENT CONNECTION OK LEAVING GAS CARD. |
|
| 12/21/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ALL SECTIONS OF SINGLE WALL VENT SHALL BE SECURED W/SCREWS THE TRANSITION OF SINGLE WALL TO DOUBLE WALL SHALL BE SECURED W/SCREWS - TAPE IS NOT ALLOWED AT THIS TRANSITION -- DOUBLE WALL VENT REQUIRES A 1" CLEARANCE FROM COMBUSTIBLE MATERIAL. |
|
| 12/20/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WATER HEATER VENT SHALL BE SECURED WITH SHEET METAL SCREWS 2) PROVIDE CORRECT VENT CAP 3) REMOVE TAPE AT TRANSITION FROM SINGLE WALL VENT CONNECTOR TO DBL WALL VENT. SECURE WITH SCREWS 4) CORRECT WATER HEATER VENT AND RECALL FINAL INSPECTION |
|
| 12/19/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*GAGE READING 0 FIND & CORRECT LEAK, PROVIDE PRESSURE TEST. |
|
| 12/15/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*PREVIOUS CORRECTIONS HAVE NOT BEEN MADE. GAS LINE DETAILS 8" 10" WATER HEATER NOT PROPERLY VENTED T & P NOT TERMINATED BONDING? |