Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/13/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 03050- NEW PIPING UNDERGROUND FROM METER UP AT BUILDING OVERHEAD TO EXISTING SERVICE ENTRY TO WATER HEATER & FURNACE ONLY OK 03090- PETITION OF APPEAL #2005-281 ON SITE GAS CARD AT METER - IN FUTURE PROVIDE TEST GAUGE IN 1/10TH POUND INCREMENTS - SW GAS 889-1888 |
|
| 12/12/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* READ ALL NOTES PROVIDE ALL LISTED ITEMS COMPLETE ALL WORK HAVE MINIMUM TEST ON SYSTEM THEN CALL FOR INSPECTION. NOTE: YOUR TOTAL DEVELOPED LENGTH IS OVER 100' AND TOTAL BTU'S ARE 116,000 PROVIDE WATER HEATER PERMIT ADDED TO THIS PERMIT. |
|
| 12/06/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* YOUR SYSTEM APPEARS TO BE UNDER SIZED PLEASE CHECK DISTANCE & TOTAL BTU DEMAND FOR PIPE SIZING |