Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 12/12/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 12/08/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :* | |
| 12/08/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE BONDING OF GAS LINE. SUPPORT PIPING ON ROOF W/WEATHER RESISTANT SUPPORTS & SECURE PIPING REPLACE LEAKING T.P VALVE AT WATER HEATER EXPOSED EXTERIOR FLUE VENT PIPING MUST BE DOUBLE WALL ABOVE ENCLOSURE. WALL FURNACE IN BEDROOM OK - ROOM HAS SUFFICIENT COMBUSTION AIR. REPLACE GAS VALVE AT WALL FURNACE SEAL WALL PENETRATION |