Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/07/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE PIPING SIZE AND OUTLETS INCREASED TO SUPPLY BOTH APPLIANCES. PRESSURE TEST ON NEW FITTINGS - OK OK FOR GAS - CALL SW GAS @ 889-1888 FOR SERVICE |
|
| 12/06/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*AIR PRESSURE TEST 15 PSI OK. APARTMENT B ONLY.CONNECT PIPING TO FURANCE AND WATER HEATER. SEALL WALL PENETRATION AT T & P REMOVE SHARP ??? FROM UNISTRUT PIPE SUPPORTS, IN LOCATION THAT MAY PRESENT A SAFETY HAZARD. ( WATER HEATER REPLACEMENT REQUIRES PERMIT) |
|
| 12/05/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*VENT FROM FURNACE TO BE DOUBLE WALL EXTENDED UP TO 2' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE AND HANG APPROVED CAP. VENT FROM WATER HEATER TO BE DOUBLE WALL THRU ROOF AND TO POINT OF TEMINATION 3' ABOVE TOP OF COOLER INTAKE WHEN WITHIN 10' OF COOLER INTAKE WITH APPROVED DOUBLE WALL VENT CAP. |