Permit: T05PL01954

Parcel: 134110420


Addresses:

7926 E 19TH PL

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/20/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
11 PSI TEST FROM METER UNDERGROUND TO STOVE, WATER HEATER, FURNACE & DRYER OK --
GAS CARD @ METER 889-1888
12/12/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE APPROVED COUPLING UNDERGROUND WITH PRIMER & THEN 10 MIL TAPE AT JOINT & TOOL MARKS
2. PROVIDE LEFT-RIGHT NIPPLE & COUPLINGS WHERE UNIONS ARE NECESSARY
3. WATER HEATER T&P DRAIN TO GRAVITY DRAIN TO DAYLIGHT
4. WATER HEATER REQUIRES MINIMUM 100 SQ.IN. LOWER COMBUSTION AIR OPENING.
5. PROVIDE AGA OR CSA VALVES AT SERVICE ENTRY & AT ALL APPLIANCES.
6. SEAL OFF FURNACE RETURN AIR OPENING IN FLOOR OR FURNACE CLOSET.
7. REMOVE TAPE FROM SINGLE TO DOUBLE WALL CONNECTION AT FURNACE VENTING IN CLOSET.
8. PROVIDE BONDING OF BUILDING GAS PIPING
RETEST GAS SYSTEM