Permit: T05PL01939

Parcel: 128070800


Addresses:

6052 E 17TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/12/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
15 PSI TEST FROM METER UNDERGROUND UP AT BUILDING OVERHEAD TO ROOF TOP UNIT + WATER HEATER ONLY
12/09/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
15 PSI TEST FROM MOTOR UNDERGROUND UP AT BUILDING OVERHEAD TO ROOFTOP UNIT & WATER HEATER ONLY - OK
1. PROVIDE PERMIT FOR WATER HEATER
2. PROVIDE PETITION OF APPEAL FOR ALTERNATE FORM OF TERMPERATURE & PRESSURE RELIEF ON SITE SIGNED BY CITY WITH CORRECT INSTALLATION.
3. PROVIDE BONDING OF BUILDING GAS PIPING
4. PROVIDE 1" MINIMUM CLEARANCE FROM COMBUSTABLES FOR WATER HEATER VENT PENETRATION THRU ROOF.
5. PROVIDE 3-GALV SCREWS AT EACH JOINT OF WATER HEATER VENT AND HAVE VENT PIPING MADE UP CORRECTLY WITH APPROVED DOUBLE WALL VENT CAP.
6. PROVIDE UPPER COMBUSTION AIR FOR WATER HEATER.
7. PLUG PAN DRAIN & INSTALL NIPPLE WITH NO THREADS ON END OF 125# PRESSURE RELIEF T&P DRAIN TO HAVE 1" CLEARANCE FROM PAN.
8. SECURE ALL PIPING CORRECTLY FOR GAS.