Permit: T05PL01927

Parcel: 130170800


Addresses:

4043 E 27TH ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/30/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
01/26/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. PLEASE HAVE AN ADULT PRESENT TO PROVIDE ACCESS ON ANY OF REINSPECTIONS -- 8:32
01/03/2006 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TEMPERATURE PRESSURE RELIEF DRAIN TO GRAVITY DRAIN TO DAYLIGHT
2. VENT FROM WATER HEATER TO HAVE 3-GALV SCREWS AT EACH JOINT, HAVE 1" MINIMUM CLEARANCE FROM COMBUSTIBLES AT PENETRATION THRU ROOF AND HAVE APPROVED VENT CAP.
3. PROVIDE MINIMUM 100 SQ. INCHES UPPER & LOWER COMBUSTION AIR OPENINGS FOR WATER HEATER.