Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
Permit Number - T05PL01914
Inspection Description - PLUMBING - GAS PRESSURE TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/22/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) ALL CORRECTIONS HAVE BEEN MADE |
|
11/30/2005 | PLUMBING - GAS PRESSURE TEST | Partial Approval | IVRS - Inspection :* GAS PRESSURE TEST. PARTIAL APPROVAL. 16 PSI AIR TEST ON GAS OK SECURE VENT PIPING W/SCREWS REMOVE TAPE AT TRANSITION TO DBL WALL REMOVE THREADS FROM T & P DRAIN PROVIDE BONDINGOF GAS LINE SEAL WALL PENETRATIONS. |