Permit: T05PL01913

Parcel: 131070340


Addresses:

6121 E 24TH ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/12/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
THIS IS NOT A REPIPE OF GAS SYSTEM
10 PSI TEST ON EXISTING GAS SYSTEM TO WATER HEATER, FURNACE & GAS LOG FIRE PLACE - OK
12/06/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*TEST SHALL HOLD FOR MINIMUM OF 10 MINUTES WITH NO PRESSURE LOSS. IS YOU REQUIRE ANY RE PIPING ENTIRE GAS SYSTEM SHALL BE BROUGHT UP TO 2003 UPC FUEL CODE REQUIREMENTS
11/29/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* GAS FLEX AT FURNACE CANNOT PENETRATE THE CABINET OF FURNACE.
CONNECT VENT TO FURNACE WITH SCREWS. PROVIDE DOUBLE WALL VENT PIPE FOR WATER HEATER & 1" CLEARANCE FROM COMBUSTIBLES.
PROVIDE MIN. 10 LB TEST ON ENTIRE SYSTEM.