Permit: T05PL01908

Parcel: 138170120


Addresses:

435 E TETON RD

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/07/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
CORRECTION HAVE BEEN MADE
OK FOR GAS
CALL SW GAS @ 889-1888
12/01/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :* PRESSURE TEST OK
STOVE, BONDING, UNION REQUIREMENTS OK
TEMPERATURE, PRESSURE RELIEF DRAIN MUST TERMINATE VERICALLY, AND MUST BE OF ONE OF THE FOLLOWING APPROVED MATERIALS. CPVC, GALV OR COPPER. PVC IS NOT ACCEPTED. PLEASE REACALL FOR FINAL INSPECTION.
11/29/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*REMOVE UNION AHEAD OF VALVE AT W.H
PROVIDE BONDING OF GAS LINE.
INSTALL T & P DRAIN TO EXTERIOR
REMOVE FLEX FROM INSIDE FIRE BOX OF STOVE.
RE PRESSURE TEST.