Permit: T05PL01898

Parcel: 138234050


Addresses:

945 W OAHU LN

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/14/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
12/09/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
3 PSI ON 30 PSI GAGE ONE POUND INCREMENTS
1. GAGE REQUIRED TO HAVE 1/10 PSI INCREMENTS
2. BONDING OF GAS LINE.
3. FURNACE FLUE VENT MUST BE DOUBLE WALL ABOVE ROOF
4. SUPPORT OVERHEAD PIPING AT CHANGE OF DIRECTION.
12/02/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*SOMEONE MUST BE HOME TO PROVIDE ACCESS.
RETURNED AT 2:30 AT REQUEST OF LARRY FROM TERRITORIAL.
NOT READY.
PROVIDE AGA VALVE AT WH.
REMOVE TRAP FROM T & P DRAIN.
CONNECT PIPING AT HOUSE.
PROVIDE BONDING OF GASLINE
PE GAS LINE NOT TO CORRECT DEPTH. CURRENTLY AT 11":
REMOVE ROCKS & CALICH FROM DITCH
PROVIDE TRACER WIRE FOR NON METALIC PIPING. RETEST 10 PSI.