Permit: T05PL01897

Parcel: 13109100A


Addresses:

5843 E 26TH ST


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05PL01897

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
12/05/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*14 PSI TEST IS OK LEFT GAS CARD ALL CORRECTIONS HAVE BEEN MADE.
11/29/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* PROVIDE TAPE PRIMER ON ALL BURIED FITTINGS PRIOR TO TAPE. LEAVE CAN OF PRIMER ON JOB SITE. PROVIDE DOUBLE WALL VENT PIPE ON WATER HEATER & EXTEND 2' ABOVE UPPER ROOF WITH AN APPROVED CAP ON TOP. MAINTAIN 1" CLEARANCE FROM COMBUSTIBLES. PROVIDE & T & P RELIEF CHAIN LINE TO DAYLIGHT.
REPLACE T & P RELIEF VALVE.
PROVIDE APPROVED GAS SHUT OFF VALVES AT ALL APPLIANCES. REMOVE THE TEE FRO WATER HEATER GAS LINE & RETEST SYSTEM. PROVIDE A BOND JUMPER ON GAS LINE TO ELEC. PANEL. GAS VALVE TO FURNACE IS OK