Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :*14 PSI TEST IS OK LEFT GAS CARD ALL CORRECTIONS HAVE BEEN MADE. | |
| 11/29/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE TAPE PRIMER ON ALL BURIED FITTINGS PRIOR TO TAPE. LEAVE CAN OF PRIMER ON JOB SITE. PROVIDE DOUBLE WALL VENT PIPE ON WATER HEATER & EXTEND 2' ABOVE UPPER ROOF WITH AN APPROVED CAP ON TOP. MAINTAIN 1" CLEARANCE FROM COMBUSTIBLES. PROVIDE & T & P RELIEF CHAIN LINE TO DAYLIGHT. REPLACE T & P RELIEF VALVE. PROVIDE APPROVED GAS SHUT OFF VALVES AT ALL APPLIANCES. REMOVE THE TEE FRO WATER HEATER GAS LINE & RETEST SYSTEM. PROVIDE A BOND JUMPER ON GAS LINE TO ELEC. PANEL. GAS VALVE TO FURNACE IS OK |