Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* | |
| 11/18/2005 | PLUMBING - GAS PRESSURE TEST | Not ready for Inspection | IVRS - Inspection :*1) UNION AT SERVICE ENTRY SHALL HAVE AGA OR CSA APPROVED GAS VALVE PRECEEDING IT OR PROVIDE LEFT-RIGHT NIPPLE & COUPLING. 2) PROVIDE BONDING OF BUILDING GAS PIPING. 3) PROVIDE AGA OR CSA APPROVED GAS VALVES AT ALL APPLIANCES 4) PROVIDE 3 GALV SCREWS AT EACH JOINT OF WATER HEATER & FURNACE FLUE VENT PIPING. 5) PROVIDE 100 SQ INCH LOWER COMBUSTION AIR FOR FURNACE. 6) SECURE GAS PIPING TO WATER HEATER. |