Permit: T05PL01856

Parcel: 106041170

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
11/21/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*REPAIR AT BLDG. SERVICE RISER/ PRESSURE TEST OK
VALVES AND FLEXES OK
OK FOR GAS
CARD LEFT AT METER
11/18/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*SYSTEM NOT HOLDING PRESSURE. PROVIDE A MIN 10 LB PRESSURE TEST TO HOLD FOR AT LEAST 15 MINUTES. AN ADULT MUST BE PRESENT AT TIME OF INSPECTION.