12/13/2005 | PLUMBING - FINAL | Approved | IVRS - Inspection :* 1) 5 PSI NO DROP IN PRESSURE 10 MINUTES |
|
11/23/2005 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*130-2PM 11/23/05 PROVIDE PRESSURE TEST 10 PSI MIN ( PRESSURE GAUGE READING 1.2 PSI) PROVIDE BONDING BETWEEN GAS & WATER PIPING PROVIDE PROTECTION FROM DAMAGE-SEE SEC. 510.6 PROVIDE CLEARANCE BETWEEN SINGLE WALL VENT CONNECTORS AND COMBUSTIBLE MATERIALS 516. 5 |