Permit: T05PL01790

Parcel: 134180160

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/07/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
11/14/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*REQUIRE 10# MINIMUM AIR TEST
HARD PIPE IN FRONT OF FURNACE BLOCKS THE ACCESS DOOR
T & P RELIEF DRAIN:MAY NOT TERMINATE IN A PAN-WHICH WON'T HOLD WATER
MAY NOT HAVE THREADS AT THE TERMINUS
CAP OFF ABANDONED PIPING
WATER HEATER AND FURNACE MUST BE ABLE TO BE REMOVED WITHOUT AFFECTING GAS PIPING
11/14/2005 PLUMBING - FINAL Partial Approval IVRS - Inspection :*10 PSI TEST IS OK
PROVIDE A BOND JUMPER TO GAS LINE
PROVIDE A PETITION OF APPEAL & 125 PSI RELIEF VALVE IN WATER SUPPLY FOR ALTERNATE METHOD OF TERMINATING T & P
PROVIDE MIN 3 SCREW IN ALL JOINTS OF VENT CONNECTORS. RECALL FOR INSPECTION