Permit: T05PL01786

Parcel: 134241430


Addresses:

633 S HARVARD AV

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
11/23/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*20 PSI TEST FROM METER UNDERGROUND TO FUTURE WATER HEATER & FURNACE & WALL HEATER OK
GAS CARD AT METER
11/21/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*NOT READY, 10 PSI TEST SHALL HOLD MINIMUM 15 MINUTES WITH NO PRESSURE LOSS.
11/14/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*GAS PIPING MAY NOT BE INSTALLED UNDERGROUND UNDER ANY BLDG.
FINISH PIPING. MAKE ALL CONNECTIONS
PROVIDE APPROVED GAS PLAN, SHOWING DEVELOPED LENGTH AND TOTAL BTU CONSUMPTION.
PROVIDE BOND BETWEEN GAS AND WATER. OK
METER WILL RELOCATE APPROX SIX FEET.NEW GAS PIPING THROUGHOUT.