Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05PL01745

Parcel: 138231650


Addresses:

771 W ELVIRA RD

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/15/2005 PLUMBING - FINAL Approved IVRS - Inspection :*
11/04/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*PROVIDE MINIMUM 10 PSI TEST TO HOLD FOR 15 MINUTES WITH NO LOSS OF PRESSURE AT TIME OF REINSPECTION
PROVIDE UPPER COMBUSTION AIR OPENING IN DOOR MINIMUM 10" X 10" WITH ?? + 100SQ INCHES
PROVIDE WATER HEATER TEMPERATURE & PRESSURE RELIEF DRAIN TO GRAVITY DRAIN TO DAYLIGHT
PROVIDE CORRECT VENT FITTINGS FOR WATER HEATER & FURNACE WITH 3-GALV SCREWS AT EACH JOINT