Permit: T05PL01744

Parcel: 133422010


Addresses:

6680 E CALLE LA PAZ

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
11/12/2005 PLUMBING - FINAL Approved IVRS - Inspection :*GAS PRESSURE TEST IS OK
ALL CORRECTIONS HAVE BEEN MADE
NOTE: OWNER SAID HE WILL
ATTACH THE BOND WIRE. MIN #6 WIRE FROM WATER SUPPLY TO GAS SUPPLY @ WATER HEATER.
11/04/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*WATER HEATER EXPANSION TANK TO BE SUPPORTED
WATER HEATER T & P DRAINS TO BE SEPARATED AND GRAVITY DRAIN TO DAYLIGHT
WATER HEATER FLUE VENT TO HAVE 3 GALV SCREWS AT EACH JOINT AND BE MADE UP CORRECTLY WITH APPROVED MATERIALS
PROVIDE ACCESS TO UPPER ROOF AND ALL UNITS
PROVIDE ROOF FLASHING ON ALL PIPE PENETRATIONS
PROVIDE WEATHER PROOF SUPPORTS FOR PIPING ON OFF WITH SECURING AT CORRECT INTERVALS.
PRIME & TAPE ALL TOOL MARKS ON UNDERGROUND PIPING