Permit: T05PL01691

Parcel: 130080990


Addresses:

3742 E GARDEN ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/25/2005 PLUMBING - FINAL Approved IVRS - Inspection :*15 PSI TEST FROM METER OVEHEAD TO FURNACE STOVE, WATER HEATER OK. GAS CARD AT METER.
10/21/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE MINIMUM 10 PSI TEST TO HOLD WITH NO PRESSURE LOSS FOR 15 MINUTES
2) VENT FROM FURNACE TO BE MADE UP CORRECTLY AT SINGLE TO DBL WALL CONNECTION WITH 3-GALV SCREWS AT EACH JOINT OF ALL APPLIANCES VENT PIPING
2) SUPPORT GAS PIPING TO FURNACE
3) WATER HEATER TEMPERATURE AND PRESSURE RELIEF TO GRAVITY DRAIN TO DAYLIGHT OR PROVIDE CITY SIGNED PETITION OF APPEAL ON SITE WITH CORRECT INSTALLATION FOR ALTERNATE FORM OF T & P RELIEF